Copyright © 2011, Tjernlund Products, Inc. All rights reserved P/N 8504174
OWNER INSTRUCTIONS, DO NOT DESTROY
Recognize this symbol as an indication of important Safety Information!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED
SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND
OPERATION OF THIS PRODUCT. READ THESE INSTRUCTIONS THOROUGHLY
BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW
THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUST-
MENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRI-
CAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, PERSONAL
INJURY OR PROPERTY DAMAGE.
!
DO NOT DESTROY. PLEASE READ CAREFULLY AND
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
MODEL DCOP1
INSTALLATION INSTRUCTIONS
REV. 3/11
TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com
UC1 VERSION
X.06
COP
CONTROL
SENSING
PORT
UC1
CONTROL
INTERIOR VIEW
Page view 0
1 2 3 4 5 6 ... 19 20

Summary of Contents

Page 1 - INSTALLATION INSTRUCTIONS

Copyright © 2011, Tjernlund Products, Inc. All rights reserved P/N 8504174OWNER INSTRUCTIONS, DO NOT DESTROYRecognize this symbol as an indication of

Page 2

9UC1 UNIVERSAL CONTROL CONNECTED WITH A SINGLE ZONE 24 VAC THERMOSTAT115VDRYWJ2 J1XLRED JUMPER POSITION MUST BE THE SAMEAS APPLIANCE INTERLOCK VOLTAGE

Page 3

10UC1 UNIVERSAL CONTROL AND WHKE INTERLOCK KIT CONNECTED WITH A MILLIVOLT APPLIANCE SWITCH ARE INCLUDED WITH WHKE KIT.950-0470 JUNCTION ADAPTER AND GA

Page 4 - 1 9

11UC1 UNIVERSAL CONTROL CONNECTED TO A HONEYWELL R7184 SERIES OR EQUIVALENTPRIMARY CONTROL WITH A LINE VOLTAGE THERMOSTAT OR AQUASTAT JumperLow Voltag

Page 5 - INSTALLED WITH

12UC1 UNIVERSAL CONTROL CONNECTED TO AN OIL-FIRED FURNACE WITH A HONEYWELL T87 OR EQUIVALENT NON-POWERED THERMOSTAT RXL XNJ1HONEYWELL T87 OR EQUIVALEN

Page 6 - FIGURE 8054007 4/14/11

13UC1 UNIVERSAL CONTROL CONNECTED WITH A HONEYWELL R8184 SERIES OR EQUIVALENT PRIMARY CONTROL AND A BURNER MOTOR POST-PURGE L2 OR B2CONNECT TOCONNECT

Page 7 - FIGURE 8052077 5-4-11

14HOW THE DRAFT COP WORKSWhen an intercepted call for heat contact closure or voltage is sensed at the UC1 interlock terminal strip the COP control is

Page 8 - PRODUCTS

154. Verify that slot on set point adjustment pot for the COP controller is aligned with the "20" hash mark, (See Diagram F).5. Disconnect t

Page 9

16ADJUSTMENT OF DRAFT SET POINT, BALANCING BAFFLE(S) AND BAROMETRIC DRAFT CONTROL(S)Sample Draft at heater manufacturer’s recommended point. If not sp

Page 10 - THERMOSTAT

17IMPORTANT: If the call for heat interlock signal or 115 VAC power is removed, the UC1 board will reset and any fault, if present,will be stored in m

Page 11 - UNIVERSAL CONTROLLER

18If faults exist check PSA-1 Prover P1 & P2 safety circuit. PSA-1 Fan Prover setpoint, DCOP1 draft setpoint or balancing of systemmay be require

Page 12

1TABLE OF CONTENTSPage (s)Description and General Information...

Page 13

19Tjernlund Products, Inc. will issue credit or provide a free part to replace one that becomes defective during the one year warrantyperiod. Proof o

Page 14 - FIGURE 8050039 3-29-11

2Failure to install, maintain and/or operate the DCOP1 in accordance with manufacturer's instructions may result in conditions which can produce

Page 15

UC1 LED STATUS & FAULT INDICATORSNDICATORSLED INDICATOR LIGHTS LED #1 (Amber) Appliance call for heat.LED #2 (Blue) Safety circuit through P1 &a

Page 16

4DCOP1 INSTALLATIONDo not mount the DCOP1 junction box on a heat source that exceeds 140OF (60OC). Examples of improper mounting surfacesinclude vent

Page 17

5SIZING A COMMON MANIFOLD SERVING MULTIPLE HEATERSThe most important step towards assuring that individual heaters vented into a common manifold draft

Page 18

6The DCOP1 must be installed by a qualified installer (anindividual properly licensed and/or trained) in accordancewith all local codes or, in their a

Page 19

7UC1 UNIVERSAL CONTROL WIRINGAll wiring from the UC1 to the appliance(s) must be appropriate Class 1 wiring as follows: installed in rigid metal condu

Page 20

8MULTIPLE APPLIANCE INTERLOCKSTo interlock with one additional 24/115 VAC heater add the MAC1E. It is a stripped down auxiliary board version of the