Copyright © 2004, Tjernlund Products, Inc. All rights reserved P/N 8504107
OWNER INSTRUCTIONS, DO NOT DESTROY
Recognize this symbol as an indication of important Safety Information!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED
SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND
OPERATION OF THIS PRODUCT. READ THESE INSTRUCTIONS THOROUGHLY
BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW
THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUST-
MENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRI-
CAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, OR PERSONAL
INJURY OR PROPERTY DAMAGE.
!
DO NOT DESTROY. PLEASE READ CAREFULLY AND
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
MODEL UC1
INSTALLATION INSTRUCTIONS
REV. C 02/04
TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com
VERSION
X.04
Page view 0
1 2 3 4 5 6 ... 14 15

Summary of Contents

Page 1 - INSTALLATION INSTRUCTIONS

Copyright © 2004, Tjernlund Products, Inc. All rights reserved P/N 8504107OWNER INSTRUCTIONS, DO NOT DESTROYRecognize this symbol as an indication of

Page 2

9AlarmA Violet0.3 A, ACOIL VALVERABlueOrangeFFWhiteTBlackRed/WhiteT115 VACBURNER MOTORIGNITION TRANS500 VA10 FLA / 60 LRALine Voltage Thermostat60 HzS

Page 3

10UC1 UNIVERSAL CONTROL CONNECTED TO AN OIL-FIRED FURNACE WITH A HONEYWELL T87 OR EQUIVALENT NON-POWERED THERMOSTAT XNRUNIVERSAL CONTROLLERREMOVE JUMP

Page 4 - 4348657 35678 345678

11UC1 UNIVERSAL CONTROL OPERATIONAL CHECK1. Confirm power is supplied to the Control. LED #5 (RED) should be on. 2. Activate the UC1 by initiating a

Page 5 - 12 12 12 12

OPERATION AND DRAFT CHECKThe installer must perform Draft Check, Safety Interlock and Combustion Air Test as outlined in the Venter installation manua

Page 6 - PRODUCTS

13LED FAULT INDICATORSFault conditions are indicated by counting the number of times LED #4 (Red) flashes.LED #4 Flashes 2 Times Fan Prover was in ele

Page 7 - D/N 9183046-8

prior to a call for heat on the SS1 Series vent systems or when using the PS1505 fan prover with a draft inducer. Keeping the Pre-Cycle Prover Status

Page 8 - THERMOSTAT

1Tjernlund Products welcomes your comments and questions. Address all correspondence to:Customer Service • Tjernlund Products, Inc. • 1601 Ninth Stre

Page 9

23. All installation restrictions and instructions in the Venter, Inducer or In-Forcer installation instructions must be adhered to when using the UC1

Page 10 - D/N 9183046-6

LED STATUS INDICATORSLED #4 & #5 (Red) Flashing Alternately = Venter in Pre-purge. (Pre-Purge options 0, 5, 20, 35 seconds)LED #4 & #5 (Red) F

Page 11

4UC1 INSTALLATIONDo not mount the UC1 junction box on a heat source that exceeds 140oF (60oC). Examples of improper mounting surfacesinclude vent pi

Page 12 - UNIVERSAL CONTROL

All wiring from the UC1 to the appliance must be appropriate Class 1 wiring as follows: installed in rigid metal conduit, intermediatemetal conduit, r

Page 13

6UC1 UNIVERSAL CONTROL CONNECTED WITH A 24 VAC ELECTRONIC IGNITION MODULEXNRUNIVERSAL CONTROLLERD/N 9183046-8115 VAC24 VACLEGEND:HONEYWELL IGNITIONCON

Page 14

7UC1 UNIVERSAL CONTROL CONNECTED WITH A SINGLE ZONE 24 VAC THERMOSTATXNRUNIVERSAL CONTROLLERTHERMOSTATGGINTERNAL CONTROLOF FURNACEWCYRRYAS APPLIANCE I

Page 15

8UC1 UNIVERSAL CONTROL CONNECTED TO A GAS OR OIL BURNER WITH AN AQUASTATXNRUNIVERSAL CONTROLLERLINE VOLTAGE OIL BURNERPRIMARY CONTROL, BURNERL1NXLJ1J2